APC E3MUPS80KHBS
Easy UPS 3M 80kVA 400V 3:3 UPS for internal batteries, Start-up 5×8
Presentation
E3MUPS80KHBS : Easy-to-install, easy-to-connect, easy-to-use, and easy-to-service 80 kVA 3-phase UPS with advanced product features, robust electrical specifications, and compact design, making business continuity easy. Ideal for small and medium data centers and other business-critical applications, this UPS is EcoStruxure-ready, providing peace of mind with cloud-based remote monitoring and management. This UPS is intended for internal batteries but is supplied without batteries, allowing you to customize the battery runtime. For detailed battery runtime information, please refer to the runtime charts under the Documents tab. Includes 5×8 start-up service.
Lead Time
- Usually ships within 6 weeks
Main Specifications
- Main Input Voltage: 400 V (3 phases)
- Other Input Voltage: 380 V, 415 V
- Main Output Voltage: 400 V (3 phases)
- Other Output Voltage: 380 V, 415 V
- Rated Power: 80 kW / 80 kVA
- Provided Equipment: Dust filter, Installation guide, Start-up service
- Product Type: Uninterruptible Power Supply (UPS)
Batteries & Runtime
- Battery Type: VRLA
- Battery Voltage: 240 V
- Number of Battery Filled Slots: 0
- Number of Battery Free Slots: 0
- Maximum Current Discharge: 222 A
Physical Specifications
- Colour: White (RAL 9003)
- Dimensions: 197 cm (H) x 60 cm (W) x 100 cm (D)
- Net Weight: 339 kg
- USB Compatible: Yes
Input Specifications
- Maximum Input Current: 104 A
- Max Short Time Withstand Current: 10 kA
- Input Harmonic Distortion: Less than 3% for full load
- Load Power Factor: 0.5 leading to 0.5 lagging without derating
- Input Power Factor: 0.99 at full load
- Input Voltage Limits: 342…477 V
- Number of Input Connectors: 1 hard wire 5-wire (3P + N + E)
- Network Frequency: 40…70 Hz
Output Specifications
- Maximum Configurable Power: 80 kVA / 80 kW
- Output Frequency: 50 Hz / 60 Hz (sync to mains)
- Harmonic Distortion: Less than 3%
- Output Harmonic Distortion: < 3% linear load and < 5% non-linear load
- Output Overload Operation: 10 minutes at 125%, 60 seconds at 150%
- UPS Type: Double conversion online
- Wave Type: Sine wave
- Bypass Type: Built-in static bypass
Conformance
- Product Certifications: CE, EAC, RCM
Environmental Specifications
- Operating Temperature: 0…40 °C
- Relative Humidity: 0…95% non-condensing
- Operating Altitude: 0…1500 ft
- Storage Temperature: -15…40 °C
- Storage Relative Humidity: 0…95% non-condensing
- Storage Altitude: 0…4572 m
- Acoustic Level: 65 dBA
- Heat Dissipation: 14850 Btu/h
- IP Protection: IP20
Communications & Management
- Control Panel: Touch screen LCD user interface
Packing Units
- Package Type: PCE
- Package Height: 210.2 cm
- Package Width: 112.5 cm
- Package Length: 75 cm
- Package Weight: 387 kg
- Number of Units in Package: 1