Vertiv ITA2-20KVA

ITA2-20KVA
Vertiv 01202683 : Liebert ITA2: 20KVA/20KW UPS, 230V, LCD, PF1.0, 3U
Long Backup model (No battery, Web Card (IS-UNITY-DP) Bundled, Rail Kit Bundled, Battery Cable Bundled)

3 Yrs On Site Replacement Warranty, not include rural area and Pattani, Ya-La, Narathiwas

3Y


ซื้อทางไลน์

 

 

 

ติดต่อเราเพื่อสั่งซื้อ สอบถาม หรือขอใบเสนอราคา
โทร : 02-140-0892
มือถือ : 089-314-3423
Line ID : @plantdigi
Email : info@plantdigi.com

SKU: ITA2-20KVA Category: Tag:
แชร์หน้านี้:

Vertiv ITA2-20KVA
01202683 : Liebert ITA2: 20KVA/20KW UPS, 230V, LCD, PF1.0, 3U
Long Backup model (No battery, Web Card (IS-UNITY-DP) Bundled, Rail Kit Bundled, Battery Cable Bundled)

Specifications:

Input Parameters:

  • Nominal Input Voltage: 380/400/415VAC 3-Phase, 4 Wire
  • Input Voltage Range: 176-288VAC at full load; 100-176VAC at linear derating; 100VAC at half load
  • Nominal Input Frequency: 50/60 Hz
  • Input Frequency Range: 40-70 Hz
  • Input Power Factor: 0.99
  • Current THD at Full Linear Load (THDi%): <3

Battery:

  • Battery Blocks Per String: 24*, 30, 32, 34, 36, 38, 40
  • Battery Charger Max. Power: 13A
  • Battery Option P/C: ITA-BCI0020K01 (built-in battery module of 16 blocks x 12V x 9Ah)
  • Battery Cabinet Dimensions (W x D x H): 430 mm x 739 mm x 85 mm

Output:

  • Nominal Output Voltage: 220/230/240VAC (1-Phase), 380/400/415VAC (3-Phase)
  • Nominal Output Frequency: 50/60 Hz
  • Rated Power Factor: Unity (1.0)
  • Voltage Harmonic Distortion: <2% for Linear loads & <5% for Non-linear loads
  • Overload Capacity: At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms
  • Crest Factor: 3:1

Efficiency:

  • Online Mode Efficiency: Up to 96.2%
  • ECO Mode Efficiency: Up to 99%

Dimensions and Weight:

  • Dimensions (W x D x H): 430 mm x 570 mm x 130 mm
  • Weight: 23 kg

General:

  • Noise at 1 m (dBA): 58
  • Operating Temperature: 0 ~ 50°C
  • Relative Humidity: 5 ~ 95%, non-condensing
  • Altitude: ≤3000m

Certifications:

  • General and Safety Requirements for UPS: IEC/EN 62040-1
  • EMC Requirements for UPS: IEC/EN 62040-2
  • UPS Classification According to IEC 62040-3: VFI-SS-111

สอบถามค่าติดตั้ง Service Installation

Shopping Cart
Scroll to Top