Vertiv ITA2-20KVA
01202683 : Liebert ITA2: 20KVA/20KW UPS, 230V, LCD, PF1.0, 3U
Long Backup model (No battery, Web Card (IS-UNITY-DP) Bundled, Rail Kit Bundled, Battery Cable Bundled)
Specifications:
Input Parameters:
- Nominal Input Voltage: 380/400/415VAC 3-Phase, 4 Wire
- Input Voltage Range: 176-288VAC at full load; 100-176VAC at linear derating; 100VAC at half load
- Nominal Input Frequency: 50/60 Hz
- Input Frequency Range: 40-70 Hz
- Input Power Factor: 0.99
- Current THD at Full Linear Load (THDi%): <3
Battery:
- Battery Blocks Per String: 24*, 30, 32, 34, 36, 38, 40
- Battery Charger Max. Power: 13A
- Battery Option P/C: ITA-BCI0020K01 (built-in battery module of 16 blocks x 12V x 9Ah)
- Battery Cabinet Dimensions (W x D x H): 430 mm x 739 mm x 85 mm
Output:
- Nominal Output Voltage: 220/230/240VAC (1-Phase), 380/400/415VAC (3-Phase)
- Nominal Output Frequency: 50/60 Hz
- Rated Power Factor: Unity (1.0)
- Voltage Harmonic Distortion: <2% for Linear loads & <5% for Non-linear loads
- Overload Capacity: At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms
- Crest Factor: 3:1
Efficiency:
- Online Mode Efficiency: Up to 96.2%
- ECO Mode Efficiency: Up to 99%
Dimensions and Weight:
- Dimensions (W x D x H): 430 mm x 570 mm x 130 mm
- Weight: 23 kg
General:
- Noise at 1 m (dBA): 58
- Operating Temperature: 0 ~ 50°C
- Relative Humidity: 5 ~ 95%, non-condensing
- Altitude: ≤3000m
Certifications:
- General and Safety Requirements for UPS: IEC/EN 62040-1
- EMC Requirements for UPS: IEC/EN 62040-2
- UPS Classification According to IEC 62040-3: VFI-SS-111