APC GVSUPS60KHS
GVSUPS60KB5HS APC Galaxy VS UPS 60kW 400V for External Batteries, Start-up 5×8
Presentation
GVSUPS60KB5HS APC Highly efficient and easy-to-deploy 60 kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5×8 start-up service and three smart modular high-capacity battery strings, expandable to five strings for extended runtime. See the battery runtime chart for details.
Lead Time
- Usually ships within 2 weeks
Main Specifications
- Main Input Voltage: 400 V (3 phases)
- Other Input Voltage: 380 V, 415 V
- Main Output Voltage: 400 V (3 phases)
- Other Output Voltage: 380 V, 415 V
- Rated Power: 60 kW / 60 kVA
- Battery Type: Internal modular battery, VRLA
- Provided Equipment: Dust filter, Installation manual, Integrated network management, Battery modules ship installed, Start-up service, EcoStruxure Ready
- Product Type: Uninterruptible Power Supply (UPS)
- Range of Product: Galaxy VS
Batteries & Runtime
- Battery Voltage: 480 V
- Discharge Battery Voltage: 384 V
- Maximum Current Discharge: 163 A
- Extended Runtime: 0
- Battery Power in VAh: 0 VAh runtime
General
- Redundant: No
Physical Specifications
- Colour: White
- Dimensions: 197 cm (H) x 55 cm (W) x 84.7 cm (D)
- Net Weight: 665 kg
- USB Compatible: No
Input Specifications
- Network Frequency: 40…70 Hz
- Input Voltage Limits: 340…460 V 400 V
- Maximum Input Current: 108 A
- Max Short Time Withstand Current: 65 kA
- Input Harmonic Distortion: Less than 3% for full load
- Load Power Factor: From 0.7 leading to 0.7 lagging without any derating
- Input Power Factor: 0.99 at full load
Output Specifications
- Maximum Configurable Power: 60 kW
- Harmonic Distortion: Less than 3%
- Output Frequency: 50 Hz sync to mains, 60 Hz sync to mains
- Crest Factor: 2.5
- Wave Type: Sine wave
- Output Voltage Tolerance: +/- 5% after 2ms, +/-1% after 50ms
- Output Harmonic Distortion: < 1% linear load and < 3% non-linear load
- Output Overload Operation: 10 minutes at 125% and 60 seconds at 150%
- Bypass Type: Built-in static bypass
Conformance
- Standards: IEC 62040-1-1, IEC 62040-2, OSHPD
Environmental Specifications
- Operating Temperature: 0…40 °C
- Relative Humidity: 0…95% non-condensing
- Operating Altitude: 0…3300 ft
- Storage Temperature: -15…40 °C
- Storage Relative Humidity: 10…80% non-condensing
- Storage Altitude: 0…3048 m
- Acoustic Level: 54 dBA
- Heat Dissipation: 7103 Btu/h
- IP Protection: IP20
Communications & Management
- Control Panel: Touch screen LCD user interface
Packing Units
- Package Type: PCE
- Package Height: 208.2 cm
- Package Width: 101 cm
- Package Length: 75.5 cm
- Package Weight: 270 kg