CyberPower SM30KPMX
30KVA Power Modular
CyberPower SM30KPMX is a power module which can be installed into the UPS to provide vertical scalability and extended power capacity for datacenter UPS. Users can choose the number of power modules to install, and flexibly configure the power capacity based on their business needs.
——–
General
——–
Phase: Three Phase
Form Factor: Modular
UPS Topology: Online Double Conversion
Energy Saving Technology: ECO Mode Efficiency > 98%
Normal Mode Efficiency ( % ): 95%
Battery Mode Efficiency ( % ): 95%
Active PFC Compatibility: Yes
Parallel Expansion (Max. Units): 20
——
Input
——
Nominal Input Voltage ( Vac ): Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Input Voltage Range ( Vac ): Line to Line (L-L): 228 ~ 478 Vac, Line to Neutral (L-N): 132 ~ 276 Vac
Configurable Voltage Range ( Vac ): Line to Line (L-L): 380 ~ 435 Vac, Line to Neutral (L-N): 220 ~ 250 Vac
Input Frequency ( Hz ): 50 ± 3, 60 ± 3
Input Frequency Range ( Hz ): 40 ~ 70
Rated Input Current ( A ): 41
Current Harmonic ( % ): 3%
Input Power Factor: 0.99
——-
Output
——-
Capacity (VA): 30000
Capacity (Watts): 27000
On Battery Waveform: Pure Sine Wave
Output Voltage Setting: Configurable
Output Frequency Setting: Configurable
Rated Output Voltage ( Vac ): Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Output Voltage Tolerance ( % ): 1 %
Output Frequency ( Hz ± % ): 50 ± 0.1, 60 ± 0.1
Power Factor: 0.9
ECO Mode Voltage Tolerance: ± 10 %
Overload Protection: Internal Current Limiting, Circuit Breaker, Fuse
Overload Protection (Line Mode): 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Battery Mode): 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Bypass Mode): 110~125% Load for 5 min, 125~150% Load for 1 min, 150~400% Load for 1 sec, >400% Load Immediately
Crest Factor: 3 : 1
Harmonic Distortion (Linear Load): THD<1%
Harmonic Distortion (Non-linear Load): THD<5.5%
Internal Bypass: Automatic Bypass, Manual Bypass
Maintenance Bypass: Yes
Typical Transfer Time ( ms ): 0
——–
Battery
——–
Recharge Power ( % ): Default 10% (Selectable from 1~20% x UPS Capacity)
Recharge Power Setting: Configurable
Charger Voltage Tolerance ( % ): ≤ 1 %
Smart Battery Management (SBM): Yes
—————————–
Surge Protection & Filtering
—————————–
EMI/RFI Filtration: Yes
—————————-
Management & Communications
—————————-
LED Indicators: Yes
———
Physical
———
Enclosure Construction: Metal
Color: Black
Ingress Protection: IP20
Rackmount Ears: Yes
————————-
Physical Size – Power Module
————————-
Dimensions (WxHxD) (mm.): 460 x 134 x 790
Weight (kg.): 34
——————–
Shipping Dimensions
——————–
Dimensions (WxHxD) (mm.): 625 x 985 x 965
Weight (kg.): 130
————–
Environmental
————–
Operating Temperature (°F): 32 ~ 104
Operating Temperature (°C): 0 ~ 40
Operating Relative Humidity (Non-condensing) ( % ): 0 ~ 95
Operating Elevation ( feet/meters ): ≤1000, Load Derated 1% per 100m from 1000m and 2000m
Storage Temperature (°F): -40 ~ 158
Storage Temperature (°C): -40 ~ 70
Storage Relative Humidity (Non-condensing) ( % ): 0 ~ 95
Audible Noise at 1.0M from Surface of Unit ( dBA ): 55
—————
Certifications
—————
Certifications: CE, IEC62040-1, IEC62040-2
—————-
Special Features
—————-
Modularity: User’s Manual
———
WARRANTY
———
Product Warranty Period (Year): 2